The update file contains the complete software for all Series 5 products. The latest software can be obtained from your country representative (www.hb-therm.com) or you can download it directly from this page. For information on how to update the software, see the instruction manual.

Software modifications

The individual software versions with their modifications are listed here and sorted according to the date of release (latest version at the top).

release

Remarks

-

New functions

  • quality test extended with HB-TP180 for HB-200/230Z2B.

improvements

  • various texts adapted in all languages.
  • various improvements in final series testing (not relevant for end customers).

Bug fixes

  • remote operation active, but cannot be deactivated as the function is not shown in the [Functions] menu (only known for units with additional ZC equipment).
  • In directly cooled units (HB-100X) with additional ZG equipment, the compressed air valve is controlled during pressure relief.

release

Remarks

  • various improvements in final series testing (not relevant for end customers).

New functions

-

improvements

-

Bug fixes

-

release

Remarks

-

New functions

  • special execution 'Safety safety cut-out via external contact':
    The unit has an additional relay that enables a safety cut-out. In normal operation, the relay is supplied with an external 24 VDC voltage. If this voltage fails, the relay falls off and switches off the unit via a potential-free contact.
  • Integration of external Flow meter Flow-5 as “integrated” [DFM Recognition] with the function [Simulate DFM As Device]:
    It is adjustable whether the temperature is transferred from the main line or from the return line of the individual measurement circuits to the machine control.

improvements

  • Measurement evaluation of flow rate measurement for water units 200/230 °C improved.
  • The ST-DOS K-374 water treatment agent was added as a pre-selectable agent.
  • The setting range for the [Sensor External Offset] parameter has been extended to -10... +10 K.

Bug fixes

  • The temperature setting is not saved if the [Temp. Nom. Value Limitation] parameter is changed.
  • Some units in Euromap 82.1 are not completely translated.
  • The switching unit Vario-5 outputs the error message “overtemperature electrical part” even though the monitoring is switched off.
  • A multiple shutdown command via Euromap 82.1 causes the temperature control unit to be switched on.
  • Sporadic edition of maintenance notifications for 200/250 °C oil units.
  • The Euromap 82.1 data model has been adapted for units without frequency control so that there are no relevant functions and actual values for frequency converter.
  • The integration of external Flow-5 Flow meter Flow-5 with more than 8 measurement circuits via protocol 1 does not work.
  • The actual value of the external sensor is always transmitted via the PROFIBUS interface, regardless of the sensor type set.

  • The measurement variables were not always compared when the measured values obtained from the quality check with the checking facility (HB-TP180/200) were adopted at a later date and not immediately after the quality check was completed.