Intervalcomponentmaintenance workqualification
when neededhousings, housing covers
  • If necessary, clean external parts with a soft, damp cloth. Do not use aggressive cleaning agent!
Operator
every 3 months/ approx. 1000 hMechanical connections
  • Check for tightness, mechanical stress and a tight fit.
  • If necessary, retract or replace
Qualified personnel
gaskets
  • Check for tightness
  • Clean or replace if necessary
every 6 months/ approx. 2000 hControl valve (RV 1.x)
  • Check for tightness, contamination and mechanical stress
  • Check function (valve closes/opens)
  • Clean or replace if necessary
Qualified personnel
Shut-off valve (AV 2, AV 3)
every 18 months/ approx. 6000 h
Temperature measurement (BT 1, BT 2)
  • Check accuracy

Qualified personnel

Pressure measurement (BP 1, BP 2)
  • Check accuracy
Flow rate measurement (BB 1, BB 2)
  • Check accuracy