All fault messages from the Flow-6 flow meter/controller are transmitted to the Interface Server Gate-6 (with additional ZV equipment) or Thermo-6 temperature control unit or another system (e.g. Machine control).

IDfaultPossible cause
Exxxsensor failure main line x
  • X531 cable unplugged, broken cable, or poor contact between cable and DFM-61 flow measurement board?
  • Temperature sensor defective?
  • DFM-61 flow measurement board defective?
Exxxsensor failure return line x
  • X540.x cable unplugged, broken cable, or poor contact between cable and DFM-61/ZFM-61 flow measurement board? (Circle 1.. 4 → DFM-61 and 5.. 8 → ZFM-61)
  • Temperature sensor defective?
  • DFM-61/ ZFM-61 flow measurement board defective? (Circle 1.. 4 → DFM-61 and 5.. 8 → ZFM-61)
E9xxsensor failure pressure BP 2
  • X532.1 cable unplugged, broken cable or poor contact between cable and DFM-61 flow measurement board?
  • BP 1 pressure sensor defective?
  • DFM-61 flow measurement board defective?
Exxxsensor failure pressure BP 4
  • X532.2 cable unplugged, broken cable or poor contact between cable and DFM-61 flow measurement board?
  • BP 2 pressure sensor defective?
  • DFM-61 flow measurement board defective?
ExxxUpper temperature deviation circle x
  • Limit value (upper set/actual deviation) set too low?
  • Control valve not opened enough?
ExxxLower temperature deviation circle x
  • Limit value (lower set/actual deviation) set too high?
  • Control valve opened too much?
ExxxReturn/main difference circle x
  • flow rate too low?
  • Limit value (Return/main difference) set too low?
  • Control valve not opened enough?
  • Heat transfer tool shape bad?
Exxxflow rate too big circle x
  • Limit value (maximum flow rate) set too low?
  • Control valve opened too much?
Exxxflow rate too low circle x
  • circuit clogged?
  • Limit value (minimal flow rate) set too high?
  • Control valve not opened enough?
Exxxflow rate deviation above circle x
  • Limit value (upper set/actual deviation) set too low?
  • Control valve opened too much?
Exxxflow deviation below circle x
  • circuit clogged?
  • Limit value (lower set/actual deviation) set too low?
  • Control valve not opened enough?
ExxxFlow-6 communication error
  • Control cable plugged in?
  • Control cable defective?
  • DFM-61 flow measurement board defective?
  • GAT-61/USR-61 control board defective?
Exxxovercurrent control valve RV 1.x
  • M 10.x step motor defective (short circuit)?
  • DFM-61/ZFM-61 flow measurement board defective? (Circle 1.. 4 → DFM-61 and 5.. 8 → ZFM-61)
ExxxRV 1.x undercurrent control valve
  • Cable X540.x unplugged, broken cable or poor contact between cable and DFM-61/ZFM-61 flow measurement board defective? (Circle 1.. 4 → DFM-61 and 5.. 8 → ZFM-61)
  • M 10.x step motor defective?
  • DFM-61/ZFM-61 flow measurement board defective?
Exxxovercurrent shut-off valve AV 2, AV 3
  • M 11 or M 12 step motor defective (short circuit)?
  • ZVB-61 extension board defective?
Exxxundercurrent shut-off valve AV 2, AV 3
  • X552/X553 cable unplugged, broken cable or poor contact between cable and ZVB-61 extension board defective?
  • M 11 or M 12 step motor faulty?
  • ZVB-61 extension board defective?
ExxxValve not recognized
  • YV 4/YV YV 5 11 magnetic coil defective?
  • X551 cable defective?
  • ZVB-61 extension board defective?