The listed maintenance work is required for optimal and trouble-free operation. If signs of increased wear are detected during regular checks, it is necessary to shorten the maintenance intervals in accordance with the actual signs of wear and tear. Maintenance intervals also vary depending on water quality, operating conditions and installation location. For further information or if you have any questions about maintenance work and maintenance intervals, please contact your HB-Therm country representative (www.hb-therm.com).

View maintenance interval

The heating, cooling, pump, fan, cooling water filter, return line filter, filling valve and air relief valve components are integrated into the integrated maintenance interval system. On the basic screen, under the maintenance symbol (), the progress of the upcoming maintenance is shown as a percentage. As soon as one of these maintenance intervals reaches 95%, the required maintenance is signaled by the warning symbol () in the register on the main screen.

Reset maintenance interval

After the maintenance work has been carried out, the corresponding maintenance interval must be reset.

  1. On the basic screen, tap on the profile button
  2. Select [User Profile] and set it to “Maintenance.”
  3. On the home basic screen, tap the menu button
  4. Select [Service] > [Maintenance] > [Reset] > [Maintenance] > [... ].
  5. Tap the reset symbol  to reset progress to 0%.

or

  1. On the home basic screen, tap the tab symbol
  2. Tap on the edit symbol in the maintenance interval display. The symbol is only visible in the “Maintenance” user profile.
    The menu level opens directly (Service > Maintenance > Reset > Maintenance).
  3. Tap the reset symbol  to reset progress to 0%.