Data is exchanged between the machine control and the Thermo-6 temperature control unit. To control system the temperature control unit via an external controller, click here...

Ethernet

The interface is the OPC UA server. A client is required for communication. This can be implemented in PC software (e.g. OPC UA Browser) or a machine control. Data is exchanged either directly between the machine control and the Thermo-6 temperature control unit or via the interface server. Gate-6

  • Ethernet interface OPC UA (EUROMAP 82.1 Release 1.01 / OPC 40082-1)
  • Switch with 2 sockets RJ-45

NOTE!

Shielded Category 5 or higher cable must be used for Ethernet connections. These cable are available from standard retailers.

USB

Connection for software updates and export/import of various unit data

  • USB-A

NOTE!

Type A USB data carriers with FAT, FAT32, exFAT and ext2/3/4 formats are supported. These USB data carriers are available at standard retailers.

HB CAN intern

HB-Therm data interface CAN for connection of flow meters Flow-5 or to Power supply to the Gate-6 interface server.

Cable pin-assignment

Alarm and external control (ZB)

The temperature control unit can be connected and controlled with the machine control system via potential-free contacts.

  • 1 Harting Han 7D plug
  • Cable for alarm contact and external control can be found in the accessories catalogue

Functions of the potential-free changeover contact:

  • Read out the unit's alarm status
  • Switch on and off the unit
  • Switch between set values (Set temperature 1, Set temperature 2)

Cable pin-assignment

function

Contactmaximum load
unit I/OAclose (signal edge)


Offopen (signal edge)
set temperature2close (signal edge)


1open (signal edge)
alarm contact-

-

250 VAC, 4 A