If the untreated water used in the heat transfer circuit meets the following guidelines, it can normally be used without special treatment.

NOTE!

To protect the system, it is recommended that you maintain these values and check them regularly.

Guideline valuesLink to Guideline values

Hydrological data

Temperature range

approximate value

unit

pH-value

-

7,5−9

-

conductivity

≤110 °C

<150

mS/m

110−180 °C

<50

>180 °C

<3

total hardness

≤140 °C

<2,7

mol/m3

<15

°dH

>140 °C

<0,02

mol/m3

<0,11

°dH

carbonate hardness

≤140 °C

<2,7

mol/m3

<15

°dH

>140 °C

<0,02

mol/m3

<0,11

°dH

chloride ions CI -

≤110 °C

<50

mg/L

110−180 °C

<30

>180 °C

<5

Sulphate SO 4 2-

-

<150

mg/L

Ammonium NH 4 +

-

<1

mg/L

Iron Fe

-

<0,2

mg/L

manganese Mn

-

<0,1

mg/L

particle size

-

<200

µm

water treatmentLink to water treatment

NOTE!

  • If the guidelines are not met, professional water treatment is required. It is recommended that the water treatment be carried out by a specialized company.