The Main line, Return line and external temperatures as well as the flow rate have a direct influence on the process and are therefore monitored. In the default setting, the limit values for process monitoring are determined and set “automatically” after each device is started, in accordance with the set monitoring level.

NOTE!

An active limit value determination is shown by the display icon for the [Reset Monitoring limits] parameter

  1. On the home basic screen, tap the menu button
  2. Select [Monitoring] > [Monitoring Type]

  3. Set the parameter to the desired value

This setting is shown on the basic screen with the monitoring symbol.

Off

There is no monitoring.
Manual

The user determines and sets the limits manual.
Automatically

The unit automatically determines and sets the limits. It is not possible to manually adjust the limit values in this setting.

NOTE!

If the monitoring type act set to “Off,” the process is not monitored. This can lead to poor production.

Guideline values when limit setting manually:

processTemperature deviationtemperature difference
Precision

3–5 K

2–3 K

Standard

5–10 K

3–5 K

Monitoring level

The parameter defines how closely the tolerances are calculated and set when limit setting (“automatically” monitoring type or reset monitoring limits).

  1. On the home basic screen, tap the menu button
  2. Select [Monitoring] > [Monitoring Level]

  3. Set the parameter to the desired value

This setting is shown on the basic screen with the monitoring symbol.

Fine

Tight tolerances for precision parts (minimal) 1,0 K

Middle

Medium tolerances for standard parts with increased requirements (minimal) 5,0 K

Rough

Large tolerances for standard parts (minimal) 10,0 K

Designation

Monitoring level

parameter reference


fine

middle

rough



factor

minimally

factor

minimally

factor

minimally


Temperature monitoring:

[Upper set/actual Deviation]

0,01

1,0 K

0,05

5,0 K

0,1

10 K

[Set temperature 1]
[Set temperature 2]

[Lower set/actual Deviation]

0,01

1,0 K

0,05

5,0 K

0,1

10 K

[Return/main difference]

1,1

1,0 K

1,5

5,0 K

2,0

10 K

[Return line]

[Main line]

[External/Main line difference]

1,1

1,0 K

1,5

5,0 K

2,0

10 K

[Main line]

[External]

[Set/actual Difference Deviation]

0,1

0,2 K

0,25

0,5 K

0,5

1,0 K

[Set Temperature Difference]

Flow monitoring:

[Maximum Flow Rate]

1,2

-

1,4

-

1,7

-

[Flow Rate]

[Minimal Flow Rate]

0,8

0,5 L/min

0,6

0,5 L/min

0,3

0,5 L/min

[Upper set/actual Deviation]

0,02

0,1 L/min

0,05

0,5 L/min

0,1

1,0 L/min

[Set Flow Rate]

[Lower set/actual Deviation]

0,02

0,1 L/min

0,05

0,5 L/min

0,1

1,0 L/min

  • Standard injection molding part with increased requirements (monitoring level = “middle”)
  • Controller on external sensor (injection mold)

DesignationCalculationvalue
set value[Set temperature 1]

-

115 °C

Measured values[External]

-

115 °C

[Main line]

-

102 °C

[Return line]

-

99 °C

[Flow Rate]

-

17 L/min

[Flow rate external 1]

-

11 L/min

[Flow rate external 2]

-

6 L/min

Calculated limits[Upper set/actual Deviation]

(0,05×115 °C)

6 K

[Lower set/actual Deviation]

(0,05×115 °C)

6 K

[Return/main difference]

(1,5×3 K)

5 K

[External/Main line difference]

(1,5×13 K)

20 K

[Maximum Flow Rate]

(1,4×17 L/min)

24 L/min

[Minimal Flow Rate]

(0,6×17 L/min)

10 L/min

Reset monitoring limits

  1. On the home basic screen, tap the menu button
  2. Select [Monitoring] > [Reset Monitoring Limits]

  3. Tap on the play symbol to start the process.

→ All limit values are automatically recalculated and set during operation, depending on the process and in accordance with the monitoring level set .

NOTE!

Limit values that are not monitored (sliders off ) are not recalculated and set.