Process monitoring
The Main line, Return line and external temperatures as well as the flow rate have a direct influence on the process and are therefore monitored. In the default setting, the limit values for process monitoring are determined and set “automatically” after each device is started, in accordance with the set monitoring level.
NOTE!
An active limit value determination is shown by the display icon for the [Reset Monitoring limits] parameter → .
- On the home basic screen, tap the menu button
Select [Monitoring] > [Monitoring Type]
- Set the parameter to the desired value
This setting is shown on the basic screen with the monitoring symbol.
Off | There is no monitoring. | |
Manual | The user determines and sets the limits manual. | |
Automatically | The unit automatically determines and sets the limits. It is not possible to manually adjust the limit values in this setting. |
NOTE!
If the monitoring type act set to “Off,” the process is not monitored. This can lead to poor production.
Guideline values when limit setting manually:
process | Temperature deviation | temperature difference |
Precision | 3–5 K | 2–3 K |
Standard | 5–10 K | 3–5 K |
Monitoring level
The parameter defines how closely the tolerances are calculated and set when limit setting (“automatically” monitoring type or reset monitoring limits).
- On the home basic screen, tap the menu button
Select [Monitoring] > [Monitoring Level]
- Set the parameter to the desired value
This setting is shown on the basic screen with the monitoring symbol.
Fine | Tight tolerances for precision parts (minimal) 1,0 K | |
Middle | Medium tolerances for standard parts with increased requirements (minimal) 5,0 K | |
Rough | Large tolerances for standard parts (minimal) 10,0 K |
Designation | Monitoring level | parameter reference | |||||
fine | middle | rough | |||||
factor | minimal | factor | minimal | factor | minimal | ||
Temperature monitoring: | |||||||
[Upper set/actual Deviation] | 0,01 | 1,0 K | 0,05 | 5,0 K | 0,1 | 10 K | [Set temperature 1] [Set temperature 2] |
[Lower set/actual Deviation] | 0,01 | 1,0 K | 0,05 | 5,0 K | 0,1 | 10 K | |
[Return/main difference] | 1,1 | 1,0 K | 1,5 | 5,0 K | 2,0 | 10 K | [Return line] [Main line] |
[Set/actual Difference Deviation] | 0,1 | 0,2 K | 0,25 | 0,5 K | 0,5 | 1,0 K | [Set Temperature Difference] |
[External/Main line difference] | 1,1 | 1,0 K | 1,5 | 5,0 K | 2,0 | 10 K | [Main line] [External] |
Flow monitoring: | |||||||
[Maximum Flow Rate] | 1,2 | - | 1,4 | - | 1,7 | - | [Flow Rate] |
[Minimal Flow Rate] | 0,8 | 0,5 L/min | 0,6 | 0,5 L/min | 0,3 | 0,5 L/min | |
[Upper set/actual Deviation] | 0,02 | 0,1 L/min | 0,05 | 0,5 L/min | 0,1 | 1,0 L/min | [Set Flow Rate] |
[Lower set/actual Deviation] | 0,02 | 0,1 L/min | 0,05 | 0,5 L/min | 0,1 | 1,0 L/min |
- Standard injection molding part with increased requirements (monitoring level = “middle”)
- Controller on external sensor (injection mold)
Designation | Calculation | value | |
Set value | [Set temperature 1] | - | 115 °C |
Measured values | [External] | - | 115 °C |
[Main line] | - | 102 °C | |
[Return line] | - | 99 °C | |
[Flow Rate] | - | 17 L/min | |
[Flow rate external 1] | - | 11 L/min | |
[Flow rate external 2] | - | 6 L/min | |
Calculated limits | [Upper set/actual Deviation] | (0,05×115 °C) | 6 K |
[Lower set/actual Deviation] | (0,05×115 °C) | 6 K | |
[Return/main difference] | (1,5×3 K) | 5 K | |
[External/Main line difference] | (1,5×13 K) | 20 K | |
[Maximum Flow Rate] | (1,4×17 L/min) | 24 L/min | |
[Minimal Flow Rate] | (0,6×17 L/min) | 10 L/min |
Reset monitoring limits
- On the home basic screen, tap the menu button
Select [Monitoring] > [Reset Monitoring Limits]
- Tap on the play symbol to start the process.
→ All limit values are automatically recalculated and set during operation, depending on the process and in accordance with the monitoring level set.
NOTE!
Limit values that are not monitored (sliders off ) are not recalculated and set.