Download page Menu structure Thermo-6.
Menu structure Thermo-6
| Main menu | Submenu 1 | Submenu 2 | Submenu 3 | Submenu 4 | Profile | Operat. release | Default | Units | Reset custom | Reset system | Reset complete |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Set values | |||||||||||
| Set temperature 1 | S | 2 | 40.0 | °C | x | x | |||||
| Set temperature 2 | S | 2 | 0.0 | °C | x | x | |||||
| Set speed | S | 2 | 100.0 | % | x | x | |||||
| Set flow rate | S | 2 | 10.0 | L/min | x | x | |||||
| Set temperature difference | S | 2 | 2.5 | K | x | x | |||||
| Set pressure difference | S | 2 | 3.0 | bar | x | x | |||||
| Heating ramp | E | 3 | Value: 5.0 Status: x | K/min | x | x | |||||
| Cooling ramp | E | 3 | Value: 5.0 Status: x | K/min | x | x | |||||
| Safety cooling temperature | E | 3 | 70.0 | °C | x | x | |||||
| Limiting temperature | E | 3 | Temperature 100: 100 Temperature 140: 140 Temperature 160: 160 Temperature 180: 180 | °C | x | x | |||||
| Flow pressure limiter | E | 3 | Value: 10.0 Status: x | bar | x | x | |||||
| Functions | |||||||||||
| Cooling | S | 1 | x | - | x | x | |||||
| Mould evacuation | S | 1 | x | - | x | x | |||||
| Remote control | S | 1 | x | - | x | x | |||||
| 2. Set value | S | 1 | x | - | x | x | |||||
| Leak stopper | S | 1 | x | - | x | x | |||||
| External sensor | S | 1 | x | - | |||||||
| Standby mode | S | 1 | x | - | x | x | |||||
| Timer | S | 1 | x | - | x | ||||||
| Display | |||||||||||
| Actual values | |||||||||||
| Set temperature (current) | S | - | - | °C | |||||||
| Main line | S | - | - | °C | |||||||
| Return line | S | - | - | °C | |||||||
| External | S | - | - | °C | |||||||
| Deviation actual/set | S | - | - | K | |||||||
| Return/main difference | S | - | - | K | |||||||
| Regulation ratio | S | - | - | % | |||||||
| Flow rate | S | - | - | L/min | |||||||
| Process power | S | - | - | kW | |||||||
| Set value system pressure | S | - | - | bar | |||||||
| System pressure | S | - | - | bar | |||||||
| Main line pressure | S | - | - | bar | |||||||
| Pump pressure differential | S | - | - | bar | |||||||
| Return pressure | S | - | - | bar | |||||||
| Pressure differential return filter | S | - | - | bar | |||||||
| Operating hours | S | - | 0.0 | h | x | ||||||
| Total current L1 | S | - | - | A | |||||||
| Total current L2 | S | - | - | A | |||||||
| Total current L3 | S | - | - | A | |||||||
| Frequency converter temperature | S | - | - | °C | |||||||
| Cooler temperature | S | - | - | °C | |||||||
| Compensation temperature | S | - | - | °C | |||||||
| External/Main line difference | S | - | - | K | |||||||
| Pump output | S | - | - | % | |||||||
| Pump speed | S | - | 0 | min-1 | |||||||
| Pump performance | S | - | - | kW | |||||||
| Pump condition | S | - | - | % | |||||||
| Position cooling valve 1 | S | - | - | % | |||||||
| Position cooling valve 2 | S | - | - | % | |||||||
| Position shut-off valve 1 | S | - | - | % | |||||||
| Remaining time pump maintenance | S | 2 | 20000.0 | h | |||||||
| Remaining time until heating maintenance | S | 2 | 20000.0 | h | |||||||
| Remaining time cooler maintenance | S | 2 | 20000.0 | h | |||||||
| Remaining time fan maintenance | S | 2 | 7000.0 | h | |||||||
| Remaining time cooling water filter maintenance | S | 2 | 1000.0 | h | |||||||
| Remaining time return filter maintenance | S | 2 | 1000.0 | h | |||||||
| Switch cycle up to maintenance air relief valve | S | 2 | 4294967295 | - | |||||||
| Switch cycle up to maintenance fill valve | S | 2 | 4294967295 | - | |||||||
| Unit information | |||||||||||
| Type of unit | S | - | - | - | |||||||
| Unit naming | S | 2 | Zone | - | x | x | |||||
| Unit location | S | 2 | - | - | x | x | |||||
| Additional equipment | S | - | - | - | |||||||
| Basic type | S | - | - | - | |||||||
| Connected load | S | - | 0.0 | kW | |||||||
| Maintenance | |||||||||||
| Heating | S | - | 0.0 | % | |||||||
| Cooling | S | - | 0.0 | % | |||||||
| Pump | S | - | 0.0 | % | |||||||
| Fan | S | - | 0.0 | % | |||||||
| Cooling water filter | S | - | 0.0 | % | |||||||
| Return line filter | S | 2 | 0.0 | % | |||||||
| Filling valve | S | - | 0.0 | % | |||||||
| Air relief valve | S | - | 0.0 | % | |||||||
| Software licenses | S | - | - | ||||||||
| Monitoring | |||||||||||
| Temperature | |||||||||||
| Upper set/actual deviation | S | 3 | Value: 5.0 Status: ✓ | K | x | x | |||||
| Lower set/actual deviation | S | 3 | Value: 5.0 Status: ✓ | K | x | x | |||||
| Return/main difference | S | 3 | Value: 10.0 Status: ✓ | K | x | x | |||||
| Set/actual difference deviation | S | 3 | Value: 2.0 Status: ✓ | K | x | x | |||||
| External/Main line difference | S | 3 | Value: 10.0 Status: x | K | x | x | |||||
| Flow rate | |||||||||||
| Maximum flow rate | S | 3 | Value: 30.0 Status: x | L/min | x | x | |||||
| Minimal flow rate | S | 3 | Value: 5.0 Status: ✓ | L/min | x | x | |||||
| Upper set/actual deviation | S | 3 | Value: 2.0 Status: x | L/min | x | x | |||||
| Lower set/actual deviation | S | 3 | Value: 2.0 Status: ✓ | L/min | x | x | |||||
| Pressure differential | |||||||||||
| Pressure difference pump above | S | 3 | Value: 1.0 Status: ✓ | bar | x | x | |||||
| Pressure difference pump below | S | 3 | Value: 1.0 Status: ✓ | bar | x | x | |||||
| Monitoring type | S | 3 | Automatically | - | x | x | |||||
| Monitoring level | S | 3 | Middle | - | x | x | |||||
| Reset monitoring limits | S | 3 | 0 | - | |||||||
| Startup-alarmsuppression | S | 3 | Complete | - | x | x | |||||
| Alarm contact function | S | 3 | NO1 | - | x | x | |||||
| Setting | |||||||||||
| Remote control | |||||||||||
| Network | |||||||||||
| Network connection status | S | - | -- | - | |||||||
| Network configuration | S | 3 | Automatically | - | x | ||||||
| IP address | S | 3 | 0 | - | x | ||||||
| Advanced network settings | |||||||||||
| Netmask | S | 3 | 0 | - | x | ||||||
| Default gateway | S | 3 | 0 | - | x | ||||||
| DNS server | S | 3 | 0 | - | x | ||||||
| MAC address | S | - | 00:00:00:00:00:00 | - | |||||||
| Current IP address | S | - | 0 | - | |||||||
| Remote control address | S | 3 | 1 | - | x | ||||||
| Remote access via VNC | E | 3 | x | - | x | ||||||
| VNC password | E | 3 | - | - | x | ||||||
| Simulate Flow as a unit | E | 3 | x | - | x | ||||||
| Local control system | U | 4 | x | - | x | x | |||||
| Active OPC UA connections | |||||||||||
| Pump control | |||||||||||
| Pump operating mode | S | 3 | Normal operation | - | x | x | |||||
| Pump start-up function | E | 3 | ✓ | - | x | x | |||||
| Set startup speed | E | 3 | 100.0 | % | x | x | |||||
| Temperature control | |||||||||||
| Internal measuring point | E | 3 | Main line | - | x | x | |||||
| Controller mode | E | 3 | Automatically | - | x | x | |||||
| Auto-tuning | E | 3 | 0 | - | |||||||
| Auto-tuning speed | E | 4 | 100.0 | % | x | x | |||||
| Output limitation heating | E | 4 | 100 | % | x | x | |||||
| Output limitation cooling | E | 4 | 100 | % | x | x | |||||
| Control parameter P internal | E | 4 | 15 | K | x | x | |||||
| Control parameter I internal | E | 4 | 60 | s | x | x | |||||
| Control parameter D internal | E | 4 | Value: 1 Status: x | s | x | x | |||||
| Control parameter P external | E | 4 | 150 | K | x | x | |||||
| Control parameter I external | E | 4 | 180 | s | x | x | |||||
| Control parameter D external | E | 4 | Value: 45 Status: ✓ | s | x | x | |||||
| Filter time external sensor Controller | E | 4 | 15.0 | s | x | x | |||||
| Disturbance factor | U | 4 | Value: 3.0 Status: x | - | x | x | |||||
| Date/time | |||||||||||
| Sync from Gate-6 | S | 3 | ✓ | - | |||||||
| Date | S | 3 | YYYY-MM-DD | - | |||||||
| Time | S | 3 | HH:MM | - | |||||||
| Time zone | S | 3 | Europe/St_Gallen | - | |||||||
| Units | |||||||||||
| Temperature-unit | S | 3 | °C | - | x | x | |||||
| Flow unit | S | 3 | L/min | - | x | x | |||||
| Pressure unit | S | 3 | bar | - | x | x | |||||
| External sensor | |||||||||||
| External sensor type | S | 3 | J/Fe-CuNi | - | x | x | x | ||||
| Pt 100 conductor circuit | U | 3 | 2 or 4 conductors | - | x | x | |||||
| Source external sensor | S | 3 | Locally | - | x | x | x | ||||
| Switch over exernal sensor | S | 3 | Automatically | - | x | x | |||||
| Infrared sensor compensation | S | 3 | x | - | x | x | |||||
| Emissivity | S | 3 | 1.0 | - | x | x | |||||
| IR temperature compensation | S | 3 | 0.0 | °C | x | x | |||||
| External sensor filter | U | 4 | 20.0 | s | x | x | |||||
| Sensor external offset | U | 4 | 0.0 | K | x | ||||||
| External sensor ascent corr. | U | 4 | 0.0 | % | x | ||||||
| Temperature at analogue min | E | 3 | 0.0 | °C | x | x | |||||
| Temperature at analogue max | E | 3 | 200.0 | °C | x | x | |||||
| Energy-efficient display | |||||||||||
| Electricity price | S | 3 | 0.27 | E/kWh | x | x | x | ||||
| Currency | S | 3 | EUR | - | x | x | x | ||||
| Operating hours/year | S | 3 | 6000 | h | x | x | x | ||||
| Miscellaneous | |||||||||||
| Cooling temperature | S | 3 | 35.0 | °C | x | x | |||||
| Waiting time after cooling | S | 3 | Value: 5 Status: x | min | x | x | |||||
| Mould evacuation time | S | 3 | ZG true: 240 | s | x | x | |||||
| Mould evacuation temperature | E | 3 | 70.0 | °C | x | x | |||||
| Delay mould evacuation after start | E | 3 | 90 | s | x | x | |||||
| Pressure relief at shutdown | E | 3 | ✓ | - | x | x | |||||
| Pressure relief duration | E | 3 | 5 | s | x | x | |||||
| Rinsing time | E | 3 | 0.5 | s | x | x | |||||
| Rinse interval | E | 3 | Value: 30 Status: x | min | x | x | |||||
| Restart interlock | E | 3 | x | - | x | x | |||||
| Show wizard at start | S | 3 | ✓ | - | x | ||||||
| Quick detection hose rupture | S | 3 | ✓ | - | x | ||||||
| Set speed Standby | S | 2 | 33.3 | % | x | x | |||||
| Safety off via ext. contact | S | 3 | x | - | x | ||||||
| Ext. contact read at mains ON | S | 3 | x | - | x | x | |||||
| Switch-off delay in case overtemperature | U | 3 | Value: 30.0 Status: x | s | x | x | |||||
| Post-cooling time | U | 3 | Value: 60 Status: ✓ | s | x | x | |||||
| Status light OK | E | 3 | x | - | x | x | |||||
| Timer | |||||||||||
| Mon-Sun switch on time | S | 3 | Value: 420 Status: x | - | x | x | |||||
| Mon-Sun switch off time | S | 3 | Value: 480 Status: x | - | x | x | |||||
| Gate | S | - | - | ||||||||
| Alarm logbook | S | - | - | ||||||||
| Save/load | |||||||||||
| Historical data | |||||||||||
| Period historical data | S | 3 | 1 day | - | x | x | |||||
| Start date | S | 3 | YYYY-MM-DD | - | |||||||
| End date | S | 3 | YYYY-MM-DD | - | |||||||
| Export historical data | |||||||||||
| Gate-6 data | |||||||||||
| Import parameter data | |||||||||||
| Import configuration data | |||||||||||
| Export parameter data | |||||||||||
| Export configuration data | |||||||||||
| Start software-update | E | 4 | - | - | |||||||
| Export analysis data | |||||||||||
| Export parameter data | |||||||||||
| Import parameter data | |||||||||||
| Export configuration data | |||||||||||
| Import configuration data | |||||||||||
| Export quality test | |||||||||||
| Help system | S | - | - | ||||||||
| Setup-wizard | S | - | - | ||||||||
| Service | |||||||||||
| Configuration | U | - | - | ||||||||
| Frequency converter | |||||||||||
| Reset complete | U | 4 | 0 | - | |||||||
| Reset History DB | U | 4 | 0 | - | |||||||
| Parameter | |||||||||||
| Cooling | |||||||||||
| Set cooler | U | 3 | 60.0 | °C | x | x | |||||
| Cooling ramp 2 | U | 4 | Value: 50.0 Status: ✓ | K/min | x | x | |||||
| Temperature cooling ramp 2 | U | 4 | 140.0 | °C | x | x | |||||
| Stepper motors | |||||||||||
| Positioning KV 1 | U | 3 | 0 | % | |||||||
| Positioning KV 2 | U | 3 | 80 | % | |||||||
| Positioning AV 1 | U | 3 | 100 | % | |||||||
| Pressure control | |||||||||||
| Pressure control mode | U | 3 | Automatically | - | x | x | |||||
| Set pressure value (manual) | U | 3 | 1.0 | bar | x | x | |||||
| Air relief pressure | U | 3 | 1.5 | bar | x | x | |||||
| Absolute pressure set value correction | U | 3 | 0.5 | bar | x | x | |||||
| Pressure setpoint correction percentage | U | 3 | 10 | % | x | x | |||||
| Pressure control hysteresis | U | 3 | 0.3 | bar | x | x | |||||
| Pressure control dead band | U | 3 | 1.7 | bar | x | x | |||||
| Filling pump control | U | 3 | Manual | - | x | x | |||||
| Filling pump switch-on pressure | U | 3 | 1.0 | bar | x | x | |||||
| Filling pump switch-on pressure (current) | U | - | - | bar | |||||||
| Set pressure value max. | U | 3 | 16.0 | bar | x | x | |||||
| Set pressure value min. | U | 3 | 0.7 | bar | x | x | |||||
| Cooling regulation ratio limit refill | U | 4 | Cooling type A2: 100 Cooling type E2: 50 | % | x | x | |||||
| Filling/air relief | |||||||||||
| Max. operating time filling pump | U | 3 | 120 | s | x | x | |||||
| Pausenfaktor filling pump | U | 3 | 25.0 | % | x | x | |||||
| Maximum fill time | U | 3 | 30 | s | x | x | |||||
| Leakage monitoring | U | 3 | Value: 300 Status: ✓ | ml/h | x | x | |||||
| Leakage monitoring reset time | U | 3 | 60 | min | x | x | |||||
| Venting efficiency | U | 3 | Pump type 6x: 1.0 Pump type 4x: 0.5 | - | x | x | |||||
| Number air relief | U | 3 | 25 | - | x | x | |||||
| Fill monitoring factor | U | 3 | 5 | - | x | x | |||||
| Reaction in case of incorrect measurements | U | 3 | Sinks | - | x | x | |||||
| Pump OFF in phase 3 | U | 3 | Pump type 6x: true Pump type 4x: false | - | x | x | |||||
| Maintenance | |||||||||||
| Heating | |||||||||||
| Factor heater overtemp. | U | 4 | 10000 | - | x | x | |||||
| Factor heater time | U | 4 | 20000 | h | x | x | |||||
| Cooling | |||||||||||
| Factor cooler time | U | 4 | 20000 | h | x | x | |||||
| Factor cooler overtemp. | U | 4 | 2000 | K/% | x | x | |||||
| Pump | |||||||||||
| Factor pump time | U | 4 | 20000 | h | x | x | |||||
| Tolerance pump condition | U | 4 | 40 | % | x | x | |||||
| Pump condition minimum | U | 4 | 60 | % | x | x | |||||
| Fan | |||||||||||
| Fan duration factor | U | 4 | 7000 | h | x | x | |||||
| Fan limit value factor | U | 4 | 30 | K/% | x | x | |||||
| CPU GIF temperature limit value | U | 4 | 80.0 | °C | x | x | |||||
| Cooling water filter | |||||||||||
| Factor cooling water filter | U | 4 | 1000 | h | x | x | |||||
| Return line filter | |||||||||||
| Limit value factor return filter | U | 4 | 1000 | h | x | x | |||||
| Reset maintenance filter limit value | U | 4 | 5.0 | % | x | x | |||||
| Valves | |||||||||||
| Factor switching cycles valves | U | 4 | 10000000 | - | x | x | |||||
| Maintenance warning threshold | U | 4 | 95 | % | x | x | |||||
| Command | |||||||||||
| Wait reset operation release | U | 3 | Value: 300 Status: ✓ | s | x | x | |||||
| Reset time menu | U | 3 | Value: 300 Status: ✓ | s | x | x | |||||
| Screensaver | U | 3 | x | - | x | x | |||||
| Heat transfer medium | |||||||||||
| Density (water) | U | 4 | 1.0 | kg/L | x | x | |||||
| Density coefficient (water) | U | 4 | -0.5 | g/L K | x | x | |||||
| Thermal capacity (water) | U | 4 | 4200 | J/kg K | x | x | |||||
| Coeff. thermal capacity (water) | U | 4 | 2.0 | J/kg K2 | x | x | |||||
| Density (oil) | U | 4 | 1.059 | kg/L | x | x | |||||
| Density coefficient (oil) | U | 4 | -0.716 | g/L K | x | x | |||||
| Thermal capacity (oil) | U | 4 | 2000 | J/kg K | x | x | |||||
| Coeff. thermal capacity (oil) | U | 4 | 4.0 | J/kg K2 | x | x | |||||
| Leak stopper | |||||||||||
| Temperature limit leak stopper | U | 3 | 70.0 | °C | x | x | |||||
| Calibrating | |||||||||||
| Pressure | |||||||||||
| Pressure sensor filter | U | 4 | 2.0 | s | x | x | |||||
| Pressure sensor 1 offset | U | 4 | 0.0 | bar | x | ||||||
| Pressure sensor 1 ascent corr. | U | 4 | 0.0 | % | x | ||||||
| Pressure sensor 2 offset | U | 4 | 0.0 | bar | x | ||||||
| Pressure sensor 2 ascent corr. | U | 4 | 0.0 | % | x | ||||||
| Pressure sensor 3 offset | U | 4 | 0.0 | bar | x | ||||||
| Pressure sensor 3 slope correction | U | 4 | 0.0 | % | x | ||||||
| Temperature | |||||||||||
| Main/return line sensor filter | U | 4 | 20.0 | s | x | x | |||||
| Main line sensor offset | U | 4 | 0.0 | K | x | ||||||
| Main line sensor ascent corr | U | 4 | 0.0 | % | x | ||||||
| Return line sensor offset | U | 4 | 0.0 | K | x | ||||||
| Return line sensor ascent corr. | U | 4 | 0.0 | % | x | ||||||
| Cooler sensor filter | U | 4 | 20.0 | s | x | x | |||||
| Cooler sensor offset | U | 4 | 0.0 | K | x | ||||||
| Cooler sensor ascent corr. | U | 4 | 0.0 | % | x | ||||||
| Tank sensor filter | U | 4 | 20.0 | s | x | x | |||||
| Tank sensor offset | U | 4 | 0.0 | K | x | ||||||
| Tank sensor incline correct | U | 4 | 0.0 | % | x | ||||||
| 1 offset backup sensor | U | 4 | 0.0 | K | x | ||||||
| Reserve sensor with 1 slope correct | U | 4 | 0.0 | % | x | ||||||
| 2 offset backup sensor | U | 4 | 0.0 | K | x | ||||||
| Reserve sensor with 2 incline corr. | U | 4 | 0.0 | % | x | ||||||
| Flow rate | |||||||||||
| Flow rate filter (internal) | U | 4 | 10.0 | s | x | x | |||||
| Flow rate offset (internal) | U | 4 | 0.0 | L/min | x | ||||||
| Flow rate ascent corr. (internal) | U | 4 | 0.0 | % | x | ||||||
| Maintenance | |||||||||||
| Actual values | |||||||||||
| Temperature CPU USR-61 | U | - | 0.0 | °C | |||||||
| Temperature CPU GIF-61 | U | - | 0.0 | °C | |||||||
| Temperature CPU ZSM-61 | U | - | 0.0 | °C | |||||||
| Operating mode (current) | U | - | Undefined | - | |||||||
| Error rate flow rate filtered | U | - | - | % | |||||||
| Heating current 1 L1 | U | - | - | A | |||||||
| Heating current 1 L2 | U | - | - | A | |||||||
| Heating current 1 L3 | U | - | - | A | |||||||
| Heating current 2 L1 | U | - | - | A | |||||||
| Heating current 2 L2 | U | - | - | A | |||||||
| Heating current 2 L3 | U | - | - | A | |||||||
| Heating current 3 L1 | U | - | - | A | |||||||
| Heating current 3 L2 | U | - | - | A | |||||||
| Heating current 3 L3 | U | - | - | A | |||||||
| Heating current 4 L1 | U | - | - | A | |||||||
| Heating current 4 L2 | U | - | - | A | |||||||
| Heating current 4 L3 | U | - | - | A | |||||||
| Heating voltage 1 L1 | U | - | - | V | |||||||
| Heating voltage 1 L2 | U | - | - | V | |||||||
| Heating voltage 1 L3 | U | - | - | V | |||||||
| Heating voltage 2 L1 | U | - | - | V | |||||||
| Heating voltage 2 L2 | U | - | - | V | |||||||
| Heating voltage 2 L3 | U | - | - | V | |||||||
| Heating voltage 3 L1 | U | - | - | V | |||||||
| Heating voltage 3 L2 | U | - | - | V | |||||||
| Heating voltage 3 L3 | U | - | - | V | |||||||
| Heating voltage 4 L1 | U | - | - | V | |||||||
| Heating voltage 4 L2 | U | - | - | V | |||||||
| Heating voltage 4 L3 | U | - | - | V | |||||||
| Heating capacity 1 L1 | U | - | - | kW | |||||||
| Heating capacity 1 L2 | U | - | - | kW | |||||||
| Heating capacity 1 L3 | U | - | - | kW | |||||||
| Heating capacity 2 L1 | U | - | - | kW | |||||||
| Heating capacity 2 L2 | U | - | - | kW | |||||||
| Heating capacity 2 L3 | U | - | - | kW | |||||||
| Heating capacity 3 L1 | U | - | - | kW | |||||||
| Heating capacity 3 L2 | U | - | - | kW | |||||||
| Heating capacity 3 L3 | U | - | - | kW | |||||||
| Heating capacity 4 L1 | U | - | - | kW | |||||||
| Heating capacity 4 L2 | U | - | - | kW | |||||||
| Heating capacity 4 L3 | U | - | - | kW | |||||||
| Regulation ratio should | U | 4 | 0.0 | % | |||||||
| Current set value controller | U | - | - | °C | |||||||
| Tank temperature | U | - | - | °C | |||||||
| Regulation ratio | U | 4 | - | % | |||||||
| Voltage 24 VAC | U | - | - | VAC | |||||||
| Voltage 24 VDC | U | - | - | VDC | |||||||
| Mains frequency (current) | U | - | - | Hz | |||||||
| Voltage 12 VDC GIF-61 | U | - | - | VDC | |||||||
| Voltage 5 VDC GIF-61 | U | - | - | VDC | |||||||
| Voltage 3.3 VDC GIF-61 | U | - | - | VDC | |||||||
| Voltage 1.8 VDC GIF-61 | U | - | - | VDC | |||||||
| Return/main difference | U | - | - | K | |||||||
| Heating current L1 | U | - | - | A | |||||||
| Heating current L2 | U | - | - | A | |||||||
| Heating current L3 | U | - | - | A | |||||||
| L1 phase heating voltage | U | - | - | V | |||||||
| L2 phase heating voltage | U | - | - | V | |||||||
| L3 phase heating voltage | U | - | - | V | |||||||
| Pump current L1 | U | - | - | A | |||||||
| Pump current L2 | U | - | - | A | |||||||
| Pump current L3 | U | - | - | A | |||||||
| Heating capacity phase 1 | U | - | - | kW | |||||||
| Heating capacity phase 2 | U | - | - | kW | |||||||
| Heating capacity phase 3 | U | - | - | kW | |||||||
| Phase power L1 | U | - | - | kW | |||||||
| Phase power L2 | U | - | - | kW | |||||||
| Phase power L3 | U | - | - | kW | |||||||
| Fan speed | U | - | 0 | min-1 | |||||||
| Pressure waste coefficient return line filter | U | - | - | - | |||||||
| Actual value controller | U | - | - | °C | |||||||
| Recognized network shape | U | - | Unknown | - | x | x | |||||
| Additional equipment | |||||||||||
| ZL, ZG, ZF, … | U | - | x | - | |||||||
| Software information | |||||||||||
| Software version | U | - | - | - | |||||||
| Software version GIF | U | - | - | - | |||||||
| Software version DMS | U | - | - | - | |||||||
| Software version ZSM 1 | U | - | - | - | |||||||
| Software version ZSM 2 | U | - | - | - | |||||||
| Software version ZSM 3 | U | - | - | - | |||||||
| Software version ZSM 4 | U | - | - | - | |||||||
| Software version FU | U | - | - | - | |||||||
| DMS software update status | U | - | -- | - | |||||||
| ZSM 1 software update status | U | - | -- | - | |||||||
| ZSM 2 software update status | U | - | -- | - | |||||||
| ZSM 3 software update status | U | - | -- | - | |||||||
| ZSM 4 software update status | U | - | -- | - | |||||||
| Boot loader version DMS | U | - | - | - | |||||||
| Hardware-version GIF/DMS | U | - | - | - | |||||||
| Serial number GIF/DMS | U | - | - | - | |||||||
| Boot loader version ZSM1 | U | - | - | - | |||||||
| Hardware-version ZSM1 | U | - | - | - | |||||||
| Serial number ZSM1 | U | - | - | - | |||||||
| Boot loader version ZSM2 | U | - | - | - | |||||||
| Hardware-version ZSM2 | U | - | - | - | |||||||
| Serial number ZSM2 | U | - | - | - | |||||||
| Boot loader version ZSM3 | U | - | - | - | |||||||
| Hardware-version ZSM3 | U | - | - | - | |||||||
| Serial number ZSM3 | U | - | - | - | |||||||
| Boot loader version ZSM4 | U | - | - | - | |||||||
| Hardware-version ZSM4 | U | - | - | - | |||||||
| Serial number ZSM4 | U | - | - | - | |||||||
| Serial number FU | U | - | - | - | |||||||
| Software version Rescue | U | - | - | - | |||||||
| Baseboard type | U | - | -- | - | |||||||
| Baseboard version | U | - | - | - | |||||||
| Baseboard serial number | U | - | - | - | |||||||
| Minimal software USR | U | - | - | - | |||||||
| Minimal Software GIF | U | - | - | - | |||||||
| minimal software GIF (USR cache) | U | - | - | - | |||||||
| Minimal Software Thermo-6 | U | - | - | - | |||||||
| Minimal software network | U | - | - | - | |||||||
| Operating hours | |||||||||||
| Operating hours unit | U | - | 0.0 | h | x | ||||||
| Operating hours pump | U | - | 0.0 | h | x | ||||||
| Operating hours cooler | U | - | 0.0 | h | x | ||||||
| Operating hours heater 1 | U | - | 0.0 | h | x | ||||||
| Operating hours heater 2 | U | - | 0.0 | h | x | ||||||
| Operating hours heater 3 | U | - | 0.0 | h | x | ||||||
| Operating hours heater 4 | U | - | 0.0 | h | x | ||||||
| Operating hours inverter | U | - | 0.0 | h | x | ||||||
| Operating hours fan | U | - | 0.0 | h | x | ||||||
| Operating hours filling pump | U | - | 0.0 | h | x | ||||||
| Statistic | |||||||||||
| Filling pump Switch cycle | U | - | 0 | - | x | ||||||
| Air relief Switch cycle | U | - | 0 | - | x | ||||||
| Filling Switch cycle | U | - | 0 | - | x | ||||||
| Mould evacuation Switch cycle | U | - | 0 | - | x | ||||||
| Leak stopper Switch cycle | U | - | 0 | - | x | ||||||
| Pressure relief Switch cycle | U | - | 0 | - | x | ||||||
| Print Switch cycle /Ventilation | U | - | 0 | - | x | ||||||
| Alarm contact Switch cycle | U | - | 0 | - | x | ||||||
| Main contactor Switch cycle | U | - | 0 | - | x | ||||||
| Total thermostat release H1 | U | - | 0 | - | x | ||||||
| Total thermostat release H2 | U | - | 0 | - | x | ||||||
| Total thermostat release H3 | U | - | 0 | - | x | ||||||
| Total thermostat release H4 | U | - | 0 | - | x | ||||||
| Act. number. trigger. Thermost. H1 | U | - | 0 | - | x | ||||||
| Act. number. trigger. Thermost. H2 | U | - | 0 | - | x | ||||||
| Act. number. trigger. Thermost. H3 | U | - | 0 | - | x | ||||||
| Act. number. trigger. Thermost. H4 | U | - | 0 | - | x | ||||||
| Number of mould evacuation | U | - | 0 | - | x | ||||||
| Status | |||||||||||
| Actuator air relief detected | U | - | x | - | |||||||
| Actuator filling detected | U | - | x | - | |||||||
| Mold emptying actuator detected | U | - | x | - | |||||||
| Actuator leak stopper detected | U | - | x | - | |||||||
| Actuator press. relief ZG detected | U | - | x | - | |||||||
| Actuator compr. air ZG detected | U | - | x | - | |||||||
| Actuator air relief active | U | 4 | x | - | |||||||
| Actuator filling active | U | 4 | x | - | |||||||
| Actuator mould evacuation active | U | 4 | x | - | |||||||
| Actuator leak stopper active | U | 4 | x | - | |||||||
| Actuator press. relief ZG active | U | 4 | x | - | |||||||
| Actuator compr. air ZG active | U | 4 | x | - | |||||||
| Actuator main contactor active | U | 4 | x | - | |||||||
| Actuator alarm contact active | U | 4 | x | - | |||||||
| Digital input 1 active | U | - | x | - | |||||||
| Digital input 2 active | U | - | x | - | |||||||
| Digital input 3 active | U | - | x | - | |||||||
| External sensor connected | U | - | x | - | |||||||
| Level measurement available | U | - | x | - | |||||||
| Horn active | U | - | x | - | |||||||
| Current error code flow rate | U | - | 0 | - | |||||||
| Current error code ZSM1 | U | - | 0 | - | |||||||
| Current error code ZSM2 | U | - | 0 | - | |||||||
| Current error code ZSM3 | U | - | 0 | - | |||||||
| Current error code ZSM4 | U | - | 0 | - | |||||||
| Current status code ZSM1 | U | - | 0 | - | |||||||
| Current status code ZSM2 | U | - | 0 | - | |||||||
| Current status code ZSM3 | U | - | 0 | - | |||||||
| Current status code ZSM4 | U | - | 0 | - | |||||||
| Filling pump status | U | 4 | x | - | |||||||
| Effective filling pump status | U | - | x | - | |||||||
| Auto-tuning active | U | - | x | - | |||||||
| Reset | |||||||||||
| Maintenance | |||||||||||
| Reset maintenance heating | U | 4 | 0 | - | |||||||
| Reset maintenance cooler | U | 4 | 0 | - | |||||||
| Reset maintenance pump | U | 4 | 0 | - | |||||||
| Reset maintenance fill valve | U | 4 | 0 | - | |||||||
| Reset maintenance air relief valve | U | 4 | 0 | - | |||||||
| Reset maintenance fan | U | 4 | 0 | - | |||||||
| Reset maintenance cooling water filter | U | 4 | 0 | - | |||||||
| Reset maintenance return filter | U | 4 | 0 | - | |||||||
| Averages | |||||||||||
| Reset average main line temp. | U | - | 0 | - | |||||||
| Reset average return line temp. | U | - | 0 | - | |||||||
| Reset average flow | U | - | 0 | - | |||||||
| Reset custom parameter | U | 4 | 0 | - | |||||||
| Reset system parameter | U | 4 | 0 | - | |||||||
| Reset logbook alarms | U | 4 | 0 | - | |||||||
| Reset historical data | U | 4 | 0 | - | |||||||
| Reset user logbook | U | 4 | 0 | - | |||||||
| Averages | |||||||||||
| Average main line temp. | U | - | 0.0 | °C | |||||||
| Average return line temp. | U | - | 0.0 | °C | |||||||
| Average flow | U | - | 0.0 | L/min | |||||||
| Simulation | |||||||||||
| Simulation operation | U | 3 | x | - | |||||||
| External process power | U | 4 | 1.0 | kW | x | x | |||||
| Activate alarm | U | 4 | Alarmlist | - | |||||||
| Disable alarm | U | 4 | Alarmlist | - | |||||||
| Number of DFM-51 | U | 4 | 0 | - | x | ||||||
| Test | |||||||||||
| Service mode | U | 3 | x | - | |||||||
| Position cooling valve 1 (Nom) | U | 4 | - | % | |||||||
| Position cooling valve 2 (Nom) | U | 4 | - | % | |||||||
| Pump status | U | 4 | x | - | |||||||
| Pump direction | U | 4 | Forwards | - | |||||||
| Position shut-off valve 1 (Nom) | U | 4 | - | % | |||||||
| Flow | |||||||||||
| Overview Flow | |||||||||||
| Flow A-D | |||||||||||
| Settings | |||||||||||
| DFM | |||||||||||
| Configuration | |||||||||||
| Calibrating | |||||||||||
| Reset | |||||||||||
| Labelling Flow | S | 3 | -- | - | |||||||
| Address range Flow | S | 3 | -- | - | |||||||
| Delete flow | S | 3 | 0 | - | |||||||
| Number measuring circuits Flow | U | 4 | - | - | |||||||
| Actual values | |||||||||||
| Main line A1..D16 | S | - | °C | ||||||||
| Return line A1..D16 | S | - | °C | ||||||||
| Return/main difference A1..D16 | S | - | K | ||||||||
| Flow rate A1..D16 | S | - | L/min | ||||||||
| Monitoring | |||||||||||
| Temperature | |||||||||||
| Return/main difference A1..D16 | S | 0 | - | K | |||||||
| Flow rate | |||||||||||
| Maximum flow rate A1..D16 | S | 0 | - | L/min | |||||||
| Minimal flow rate A1..D16 | S | 0 | - | L/min | |||||||
| Reset | |||||||||||
| Reset complete | U | 4 | 0 | - | |||||||
| Reset system parameter | U | 4 | 0 | - | |||||||
| Measuring circuit active A1..D16 | S | 3 | x | - | x | ||||||
| User logbook | S | - | - | ||||||||
| Quality check | |||||||||||
| Tolerances | |||||||||||
| Tolerance flow rate measurement | U | 4 | 10.0 | % | x | x | |||||
| Tolerance pressure measurement | U | 4 | 0.1 | bar | x | x | |||||
| Tolerance pressure gauge | U | 4 | 0.5 | bar | x | x | |||||
| Tol. temp. measurement internal | U | 4 | 1.0 | K | x | x | |||||
| Tol. temp. measurement external | U | 4 | 6.0 | K | x | x | |||||
| Tolerance external sensor Pt 100 | U | 4 | 3.0 | K | x | x | |||||
| Tolerance pump pressure | U | 4 | 30 | % | x | x | |||||
| Maximum heat-up time | U | 4 | 15 | min | x | x | |||||
| Maximum cooling time | U | 4 | 10 | min | x | x | |||||
| Start quality test | U | 4 | 0 | - | |||||||
| Test temperature 3 | U | 4 | Value: 60.0 Status: x | °C | x | x | |||||
| Test temperature 4 | U | 4 | Value: 80.0 Status: x | °C | x | x | |||||
| Apply calibrating | U | 4 | 0 | - | |||||||
| Profile | |||||||||||
| Language | S | 0 | English | - | x | ||||||
| User profile | S | 4 | Standard | - | x | x | |||||
| Change code | S | 4 | 1234 | - | x | x | |||||
| Operating release | S | 4 | 2 | - | x | x | |||||
| Horn volume | E | 3 | 10 | - | x | x | |||||
| Screen brightness | S | 3 | 65 | % | x | x |