The update file contains the complete software for all Series 5 products. The latest software can be obtained from your country representative (www.hb-therm.com) or you can download it directly from this page. For information on how to update the software, see the instruction manual.
The individual software versions with their modifications are listed here and sorted by date of release (latest version at the top).
Release
Remarks
-
New Functions
Special setting for type of unit HB-140ZM4E1
The maximum temperature is limited to 120°C. Reason: A safety thermostat is used with a maximum temperature of 130°C. As a result, the unit cannot be operated at a set value above 120°C.
Improvements
Phase detection in the event of faults on the power grid
In power grids with faults (harmonics caused, for example, by frequency converter in the same power grid), phase detection may be faulty when the unit is started. As a result, the error message E014 (phase missing) appears.
Mould evacuation with compressed air for housing size 4 units
The functional sequence for drain into the compressed air outlet has been adjusted.
Various improvements to final series testing (not relevant for end customers)
Measurement evaluation of Flow rate measurement for water units 200/230 °C improved
An adjusted tolerance value is taken into account for the edition of the error message E050 (flow rate zero); the system reacts less sensitively.
Bug fixes
parameter setting for Cleaning Unit Clean-5
The parameter ([Set value Level], [PurgeSet value Level]) Are reset to thedefault settings after the network off/on. Changes to these parameter are not saved permanently.
Function [Simulate DFM As Device]
The act values (temperature, flow rate) of external measurement circuits are not displayed when more than 4 measurement circuits are used (e.g. 8-way manifold). From the 5th measuring circuit on, the display of the act values on the machine controls does not work.
Euromap 82.1 − control parameter (P, I, D)
The value input is not accepted if the control parameter P, I, D are changed individually and the same value is entered for all of them.
Release
Remarks
-
New Functions
Quality test extended with HB-TP180 for HB-200/230Z2B.
Improvements
Various texts adapted in all languages.
Various improvements in final series testing (not relevant for end customers).
Bug fixes
Remote operation active, but cannot be deactivated as the function is not shown in the [Functions] menu (only known for units with additional ZC equipment).
In directly cooled units (HB-100X) with additional ZG equipment, the compressed air valve is controlled during pressure relief.
Release
Remarks
Various improvements in final series testing (not relevant for end customers).
New Functions
-
Improvements
-
Bug fixes
-
Release
Remarks
-
New Functions
Special execution 'Safety safety cut-out via external contact': The unit has an additional relay that enables a safety cut-out. In normal operation, the relay is supplied with an external 24 VDC voltage. If this voltage fails, the relay falls off and switches off the unit via a potential-free contact.
Integration of external Flow Meter Flow-5 as “integrated” [DFM Recognition] with the function [Simulate DFMAs Device]: It is adjustable whether the temperature is transferred from the Main line or from the Return line of the individual measurement circuits to the machine control.
Improvements
Measurement evaluation of Flow rate measurement for water units 200/230 °C improved.
The ST-DOS K-374 water treatment agent was added as a pre-selectable agent.
The setting range for the [Sensor External Offset] parameter is extended to -10... +10 K.
Bug fixes
The temperature setting is not saved if the [Temp. Nom. Value Limitation] parameter is changed.
Some units in Euromap 82.1 are not completely translated.
The switching unit Vario-5 outputs the error message “overtemperature electrical part” even though the monitoring is switched off.
A multiple shutdown command via Euromap 82.1 causes the temperature control unit to be switch on.
Sporadic edition of maintenance notifications for 200/250 °C oil units.
The Euromap 82.1 data model has been adapted for units without frequency control so that there are no relevant functions and actual values for frequency converter.
The integration of external Flow-5 Flow Meter Flow-5 with more than 8 measurement circuits via protocol 1 does not work.
The actual value of the external sensor is always transmitted via the PROFIBUS interface, regardless of the sensor type set.
The measurement variables were not always compared when the measured values obtained from the quality check with the checking facility (HB-TP180/200) were adopted at a later date and not immediately after the quality check was completed.
Datenschutz - Data protection - Protection de données
Wir setzen Cookies ein, um Ihnen die Nutzung unserer Webseite zu erleichtern. Weitere Informationen zu Cookies finden Sie in unserer Datenschutzerklärung. We use cookies to help you use our website. More information about cookies can be found in our privacy policy. Notre site utilise des cookies afin de vous garantir un service optimal. En utilisant ce site web, vous acceptez les présentes conditions. Vous trouverez privacy policy de plus amples informations. Privacy Policy